Note: The possibility of a writing command on the registers
0000 to 005F depends on the configuration. With the following
channel types a writing command is valid if this has been al-
lowed by the Configuration Software.
Digital Counter with Reset Function:
After a write command to this channel the counter will be set to
zero.
Arithmetic Variable with min/max-Function and Reset Function:
After a write command to this channel the pull-pointer will be
reset.
Setpoint Variable:
After a write command to this channel the new value will be
set.
Digital Output Variable (Host Output):
A write command to this channel will set the corresponding
channel to '1' or '0' respectively.
Device information
Register Type Contents Range
0300 ro Number of channels 2 Byte
0301..0303 ro Serial number 6 Char
0304..030D ro Location 20 Char
Device identification
Register Type Contents Range
0400..0404 ro Vendor name ("Friedrichs") 10 Char
0405..0408 ro Model name ("COMBILOG") 8 Char
0409..040C ro HW-revision ("xy.yy___") 8 Char
040D..0410 ro SW-revision ("xy.yy___") 8 Char